Keywords
Heat recovery ventilator, Evaporative cooling, Air handling unit, Energy efficiency, Heating ventilation and air conditioning, Indirect evaporative cooling
Document Type
Article
Abstract
This study investigates the energy and environmental performance of a hospital air handling unit integrated with a plate heat recovery ventilation (HRV) system and return-air evaporative cooling under hot climatic conditions. The evaporative cooling (EC) stage is applied to the return/exhaust air before the plate heat exchanger, reducing its temperature and enhancing the sensible heat recovery process. The results show that the cooling load of the conventional system reaches a maximum of 39.67 kW, while the proposed HRV+EC configuration achieves a maximum cooling capacity reduction of 18.23 kW. The annual electricity consumption decreases from approximately 17,700 to 9,600 kWh/year, corresponding to a reduction of about 46%. The associated annual CO2 emissions decrease from approximately 11 to 6 tons/year, equivalent to a reduction of approximately 45%. The results demonstrate that combining return-air evaporative cooling with heat recovery can substantially reduce cooling demand, electricity consumption, and the associated environmental impact of hospital HVAC systems operating in hot climates.
Recommended Citation
Mohamed, Mustafa Hussin; Abbood, Mohammed Hassan; and Mohammed, Hayder Noori
(2027)
"Energy and Environmental Analysis of a Heat Recovery Ventilation System with Return-Air Evaporative Cooling in Hospital Air Handling Units,"
Engineering and Technology Journal: Vol. 45:
Iss.
1, Article 3.
DOI: https://doi.org/10.30684/2412-0758.2432
DOI
10.30684/2412-0758.2432
First Page
41
Last Page
58